Amp to kVA calculator for factories (3 phase, Malaysia)
Factory listings in Malaysia show power supply in Amp. Use this to see what that means in kVA and kW, or add up your machines to find how many Amp you need before you rent or buy.
Convert Amp to kVA, kVA to Amp and kW to Amp
This calculator uses a 3-phase 415 V supply, the voltage on factory switchboards.
139 factories on our website have at least 600 Amp (51 for rent, 92 for sale).
See these factories →How many Amp does my factory need?
Your machines Example – change to yours
| Machine or load | kW each | Qty |
|---|
Most engineers leave 20–25% spare, so the main breaker does not run at full load and you can add machines later. Use 0% if you will not add any.
The kW is on each machine’s nameplate or spec sheet. This adds everything as if it runs at once, which is usually more than a factory uses at any moment, so the answer is on the safe side. If a machine shows only Amp or kVA, ask the supplier for its kW.
- Total machine load
- –
- Needed capacity
- –
- With extra for future machines
- –
– on our website have enough power.
See these factories →Amp to kVA chart (3 phase, 415 V)
| Main switchboard | Supply capacity | Machines it can run (power factor 0.85) |
|---|---|---|
| 100 Amp | 72 kVA | 61 kW |
| 200 Amp | 144 kVA | 122 kW |
| 300 Amp | 216 kVA | 183 kW |
| 400 Amp | 288 kVA | 244 kW |
| 600 Amp | 431 kVA | 367 kW |
| 800 Amp | 575 kVA | 489 kW |
| 1,000 Amp | 719 kVA | 611 kW |
| 1,500 Amp | 1,078 kVA | 916 kW |
| 2,000 Amp | 1,438 kVA | 1,222 kW |
| 3,000 Amp | 2,156 kVA | 1,833 kW |
Amp, kVA and kW questions
How do I convert Amp to kVA (3 phase)?
For a 3-phase 415 V supply, kVA = 1.732 × 415 × Amp ÷ 1,000, which is about 0.72 kVA for each Amp. So 400 Amp is about 288 kVA and 1,000 Amp is about 719 kVA.
How do I convert kVA or kW to Amps?
At 415 V three phase, Amp = kVA × 1,000 ÷ (1.732 × 415), which is about 1.39 Amp for each kVA. So 500 kVA is about 696 Amp. For kW, first divide by the power factor: 300 kW ÷ 0.85 = 353 kVA, which is about 491 Amp.
What is the difference between kVA and kW?
kVA is the capacity of the supply. kW is the real power your machines use. Motors, compressors and air-conditioning take part of the supply without doing work, so kW is lower: kW = kVA × power factor. TNB requires customers supplied at 33 kV or below to keep a power factor of at least 0.85, or pay a surcharge, so this calculator uses 0.85. A 719 kVA supply runs about 611 kW of machines.
A listing says 2,000 Amp and 11 kV. What does that mean?
11 kV (11,000 volts) is the voltage of the TNB line coming into the factory. The factory’s own substation steps it down to 415 V for the machines, and 2,000 Amp is the size of the main switchboard on that 415 V side, about 1,438 kVA. Large factories are supplied this way, and they pay the medium voltage tariff.
When does a factory need its own TNB substation?
Under TNB’s connection guidelines, a load above 350 kVA (about 487 Amp at 415 V) is fed by underground cable from a new substation, and a load of 1,000 kVA or more (about 1,391 Amp) is supplied at medium voltage, 11 kV to 33 kV, through a TNB switching station. TNB decides the final scheme after a system study.
What if the factory does not have enough power?
Ask the owner whether TNB can upgrade the supply, who pays for it, and how long it takes. An upgrade that needs a new substation takes months, so check this before you sign.
Does more power mean a higher electricity bill?
On low voltage, you pay for the kWh you use. On medium voltage, TNB also charges for your maximum demand each month, so your peak load matters. See our guide to factory electricity tariffs.